FLOWX IFLOWX
Brand: Endress+HauserFLOWX IFLOWX
Brand: Endress+Hauser
Xpert Specs at a Glance
Number of applications:
Support up to 4 gas runs or 2 liquid runs per module (Flow-X/M, Flow-X/C)
Outputs:
4x analog output for process outputs and flow / pressure control. Resolution 14 bits, 0.075% FS.
Analog outputs share same ground floating in relation to all other electronics.
16x digital output, open collector. Rating 100mA @24V
Analog outputs share same ground floating in relation to all other electronics.
16x digital output, open collector. Rating 100mA @24V
Inputs:
6x analog transmitter input, high accuracy
Input types are 4 to 20 mA, 0 to 20 mA, 0 to 5 V, 1 to 5 V
Accuracy mA inputs; 0.002% FS at 21 °C, 0.008% at full ambient range of 0-60 °C, long-term
stability 0.01% per year
Resolution: 24 bits. Analog inputs have the same earthing relative to all other electronic devices.
16x digital status inputs. Resolution 100ns (10MHz)
Input types are 4 to 20 mA, 0 to 20 mA, 0 to 5 V, 1 to 5 V
Accuracy mA inputs; 0.002% FS at 21 °C, 0.008% at full ambient range of 0-60 °C, long-term
stability 0.01% per year
Resolution: 24 bits. Analog inputs have the same earthing relative to all other electronic devices.
16x digital status inputs. Resolution 100ns (10MHz)
Field of application
The Flow-X flow computer provides gas volume conversion, event logging, parameter logging, and reports using state-of-the-art technology. Identical modules are combined in different housings, offering a multi-stream version Flow-X/P for 1 - 4 measuring distances with a local touch screen, or the version Flow-X/S for smaller installations with one measuring distance. It is the ideal partner for custody transfer gas metering solutions in installations with FLOWSIC600 ultrasonic gas flowmeters.
Custody gas metering
Demanding natural gas and process gas applications
Device properties:
- MID approved configuration for gas metering streams with FLOWSIC600
- Powerful modules for demanding applications
- Each module features CPU, memory and equal in/outputs
- Intuitive user interface for graphics display and web browser
- True remote access via Ethernet
- Station computer for multiple streams
Key Benefits
- Reduced planning and installation costs through standard configurations
- Very accurate volume conversion with multiple calculation cycles per second
- High reliability through independent modules with their own volume conversion and storage of measured values, counter readings and events
- Easy extension of installations with modules featuring equal in/outputs and 100% software configuration
- Reduced service and maintenance costs with tamper-proof remote maintenance
- Cost-efficient and flexible system integration of multiple streams
Specifications
Brand
Industry
- Power & Energy
- Oil & Gas
Gas
Measuring variables
- gas volume conversion, event logging, parameter logging, and reports
Number of applications
- Support up to 4 gas runs or 2 liquid runs per module (Flow-X/M, Flow-X/C)
Calculations
- Gas property calculations:
- AGA 5, AGA 8 Part 1, AGA 8 Part 2 (GERG-2008), AGA 10
- AGA NX-19
- GERG-2008
- GERG91mod (GOST 30319.2-1996)
- GOST 30319.2-2015
- GSSSD MR-113
- ISO 6976, ISO 12213 Parts 2 and 3
- S-GERG
- Flow rate calculations:
- AGA 3, AGA 7, AGA 9, AGA 11
Electrical connection
- Voltage
- 24 V DC (± 10%), with redundant connections
- Current consumption:
- Flow-X/P0, X/M, X/S: ≤ 0.4 A nominal; ≤ 0.8 A maximal
- Flow-X/C: ≤ 0.6 A nominal; ≤ 1.0 A maximal
Ambient temperature range
- Flow-X/S: -40 °C ... +75 °C
- Flow-X/C, Flow-X/P, Flow-X/R: 0 °C ... +60 °C
System
- CPU and memory: 800 MHz, 512 MB RAM, 1 GB flash memory
- Clock: Real-time clock, accuracy better than 1 sec/day
- Gold cap for date and time retention
- Watchdog: Hardware and software watchdog timer
- Tamper switch: Mechanical tamper switch to prevent changing of the application and vital parameters within
- that application
Supported gas chromatographs
- Supports all common gas chromatographs (including ABB NGC8200 series, ABB BTU8100,
- Danalyser, Yamatake HGC, Encal 3000, Angus GQA, Siemens Maxum and Sitrans)
Conformities
- 2014/32/EU Measuring Instruments Directive (MID)
- Directive 2014/30 / EC relating to electromagnetic compatibility
- 2012/19/EU WEEE Directive (WEEE 2)
- 2011/65/EU RoHS
- OIML R117-1
- WELMEC 7.2, 8.3, 8.8
- API 21.1
Hazardous area approvals
- Applies for FlowX/M and X/S only
- Class I, Division 2, Groups A, B, C, and D, T4
- Class I, Zone 2, Group IIC, T4
- IECEx Ex ec IIC Gc
- ATEX II 3 G Ex ec IIC Gc
Inputs
- 6x analog transmitter input, high accuracy
- Input types are 4 to 20 mA, 0 to 20 mA, 0 to 5 V, 1 to 5 V
- Accuracy mA inputs; 0.002% FS at 21 °C, 0.008% at full ambient range of 0-60 °C, long-term
- stability 0.01% per year
- Resolution: 24 bits. Analog inputs have the same earthing relative to all other electronic devices.
- 16x digital status inputs. Resolution 100ns (10MHz)
Outputs
- 4x analog output for process outputs and flow / pressure control. Resolution 14 bits, 0.075% FS.
- Analog outputs share same ground floating in relation to all other electronics.
- 16x digital output, open collector. Rating 100mA @24V